Our products
Single-sided service assembled chambers KSO2-10
Single-sided service assembled chambers KSO2-10 (hereinafter KSO2-10 chambers) are designed for equipping indoor switchgears with frequent switching operations, protecting outgoing lines against overload currents and short-circuit currents, and ensuring power supply continuity. KSO2-10 chambers are used in three-phase AC electrical networks rated at 6(10) kV, 50 Hz for systems with isolated or arc-suppression reactor grounded neutral.
KSO2-10 chambers are designed to replace KSO-292, KSO-285, and KSO-272 chambers and feature several advantages over previously manufactured KSO-2 series chambers:
- increased operational reliability due to the use of modern high-voltage switching devices (vacuum circuit breakers) with high mechanical and switching endurance;
- relay protection is provided by multifunctional, compact, and highly reliable microprocessor units;
- enhanced operational safety due to the use of more reliable interlocks of high-voltage switching devices against erroneous actions of substation personnel during switching and repair operations, placement of auxiliary circuit equipment in a separate removable relay cabinet completely isolated from primary circuits, and location of busbars inside the chamber with top shielding by a protective hinged metal panel.
Single-sided service assembled chambers KSO2-10 comply with current regulatory documents in the Republic of Kazakhstan. The compliance of KSO2-10 chambers with standards, quality, and safety requirements is confirmed by the Certificate of Conformity of the State Certification System of the Republic of Kazakhstan (voluntary certification).
Main parameters of KSO2-10 chambers |
|
| Parameter / Description | Value / Rating |
|---|---|
| Rated voltage, kV | 6; 10 |
| Maximum operating voltage, kV | 7,2; 12 |
| Rated busbar current, A | 6630, 1000, 1600 |
| Rated current of main chamber circuits, A | 20, 32, 630; 1000; 16001 |
| Rated current of main circuits with load switches, voltage transformers, power transformers, and fuses, AА | 630 |
| Rated breaking current of main switching devices | 20,0; 25,02,10,02 |
| Rated electrodynamic withstand current of main circuits (peak), kA | 51,03 |
| Thermal withstand current (3 sec), kA | 20,03 |
| Rated voltage of secondary circuits, И | 220 220 |
| Insulation type | Air |
| Connection type | Cable or busbar |
| Maintenance conditions | Single-sided |
| Degree of enclosure protection according to GOST 14254-96 | IР30 - with closed upper and lower chamber doors from the front; IР00 - with open doors and from the rear side. |
1 Chambers with rated current exceeding 1600 A can only be custom-manufactured.
2 According to the technical specifications of the circuit breakers;
3 Thermal and electrodynamic withstand of current transformers according to their technical parameters.