KSO2-10

KSO2-10

Complete distribution devices of internal installation (KRU)

Leave a request

Single-sided service assembled chambers KSO2-10


Single-sided service assembled chambers KSO2-10 (hereinafter KSO2-10 chambers) are designed for equipping indoor switchgears with frequent switching operations, protecting outgoing lines against overload currents and short-circuit currents, and ensuring power supply continuity. KSO2-10 chambers are used in three-phase AC electrical networks rated at 6(10) kV, 50 Hz for systems with isolated or arc-suppression reactor grounded neutral.

KSO2-10 chambers are designed to replace KSO-292, KSO-285, and KSO-272 chambers and feature several advantages over previously manufactured KSO-2 series chambers:

  • increased operational reliability due to the use of modern high-voltage switching devices (vacuum circuit breakers) with high mechanical and switching endurance;
  • relay protection is provided by multifunctional, compact, and highly reliable microprocessor units;
  • enhanced operational safety due to the use of more reliable interlocks of high-voltage switching devices against erroneous actions of substation personnel during switching and repair operations, placement of auxiliary circuit equipment in a separate removable relay cabinet completely isolated from primary circuits, and location of busbars inside the chamber with top shielding by a protective hinged metal panel.

Single-sided service assembled chambers KSO2-10 comply with current regulatory documents in the Republic of Kazakhstan. The compliance of KSO2-10 chambers with standards, quality, and safety requirements is confirmed by the Certificate of Conformity of the State Certification System of the Republic of Kazakhstan (voluntary certification).

Main parameters of KSO2-10 chambers

Parameter / DescriptionValue / Rating
Rated voltage, kV 6; 10
Maximum operating voltage, kV 7,2; 12
Rated busbar current, A 6630, 1000, 1600
Rated current of main chamber circuits, A 20, 32, 630; 1000; 16001
Rated current of main circuits with load switches, voltage transformers, power transformers, and fuses, AА 630
Rated breaking current of main switching devices 20,0; 25,02,10,02
Rated electrodynamic withstand current of main circuits (peak), kA 51,03
Thermal withstand current (3 sec), kA 20,03
Rated voltage of secondary circuits, И 220 220
Insulation type Air
Connection type Cable or busbar
Maintenance conditions Single-sided
Degree of enclosure protection according to GOST 14254-96 IР30 - with closed upper and lower chamber doors from the front;
IР00 - with open doors and from the rear side.

1 Chambers with rated current exceeding 1600 A can only be custom-manufactured.
2 According to the technical specifications of the circuit breakers;
3 Thermal and electrodynamic withstand of current transformers according to their technical parameters.