Our products
Complete switchgear cabinets of the KM-1KF series
Indoor double-sided service complete switchgear units (KRU) KM-1KF are designed for receiving and distributing three-phase AC electrical energy at frequency of 50 and 60 Hz at rated voltage of 6 and 10 kV.
KM-1KF switchgear cabinets are used in auxiliary distribution gear of power plants, electrical substations of power systems and industrial enterprises, as well as in power supply facilities of vital agricultural consumers.
KM-1KF series cabinets are designed to operate under the following conditions::
- Installation altitude of KM-1KF cabinets above sea level - no more than 1000 m (use of switchgear cabinets at altitudes above 1000 m is allowed subject to compliance with GOST 15150-69, GOST 1516.1-76 and GOST 8024-90);
- In areas with seismicity not exceeding 9 points on the MSK-64 scale (GOST 17516.1-90);
- Rated values of environmental climatic factors according to GOST 15543.1-89 and 15150-69 for version U3;
- Ambient air temperature in the switchgear room from - 5° C to +40° C (at ambient air temperature below - 5° C heaters must be installed by the user in the switchgear room);
- Environment - non-explosive, free of conductive dust, aggressive gases or vapors in concentrations that destroy metals and insulation.
- Rated operation mode – continuous;
- Operating position in space - vertical, permissible deviation - no more than + 5 degrees from vertical;
- Heating temperature of cabinet enclosure parts accessible during operation in rated mode shall not exceed 50° C (GOST 14693-90);
- Upper heating temperature threshold of contact connections during operation is 75° C (GOST 8024-90).
Technical specifications and main designs of KM-1KF series cabinets |
|
| Parameter / Description | Value / Rating |
|---|---|
| Maximum operating voltage, kV | 7,2; 12 |
| Rated voltage, kV | 6,0; 10,0 |
| Rated current of main cabinet circuits, A | 630; 1000; 1250; 1600; 2000; 2500 |
| Rated current of main circuits with voltage transformers, power transformers, and fuses, A | 630 |
| Busbar rated current, A | 630; 1000; 1250; 2000; 2500 |
| Thermal withstand current for 3 sec duration, kA | 20-31,5 |
| Electrodynamic withstand of main circuits, kA | 51-81 |
| Maintenance conditions | double-sided |
| Inlet configurations | cable, busbar |
| Main cabinet types depending on built-in equipment and connections (main cabinet types listed) |
SHVV - with vacuum circuit breaker SHTN - with voltage transformers SHR - with separable contact connections SHPS - cabinet with power fuses SHKS - cabinet with cable assembly SHST - cabinet with power transformer SHNVA - cabinet with low-voltage equipment (auxiliary supply) SHSN - standalone auxiliary power cabinet |
| Degree of protection according to GOST 14254-96 | IP31 - with closed doors IP00 - with open doors or without doors |