lectrical characteristics
Switchgears CS KER 24/1 are assembled at the KazEnergoPower plant, have passed type tests, switchgears in a metal case for indoor installation.
Structure and design
Partition class |
PM (metal partitions) |
Availability category in cell service
cable connection cells |
LSC 2 LSC 2 LSC 1 |
Compartment accessibility (shell)
|
|
Internal arc certification (optional)
The following internal arc tests are carried out: |
|
IAC |
= Classification according to internal arc resistance |
Class IAC at
|
Rated voltage from 7.2 kV to 24 kV: IAC A FL, I SC, t |
Availability type: A |
The device is located in a closed electrical |
|
production site, only for |
|
authorized personnel |
|
(according to IEC 62271-200) |
– F |
Front side |
– L |
Side surfaces |
–R |
Rear panel (free-standing) |
Arc test current I SC |
up to 21 kA |
Test duration t |
1 s |