Distribution devices of the CS-MN series are designed for the distribution of electrical energy in networks with a voltage of 6 kV with an isolated neutral with a frequency of 50 Hz, protection of electrical installations and control of underground electrical receivers in iron ore and coal mines. CS-MN multi-cabinet, indoor installation, stationary, double-sided service, with withdrawable elements, with local and remote control. CS-MN cabinets are used to complete distribution points and can be connected into separate sections. The sections are connected to each other by a sectional cabinet. The distribution point may consist of one, two or three sections. CS-MN cabinets and the products attached to them are of normal mine design.
Cabinets of the CS-MN series comply with the requirements of GOST 24754-2013 (regarding the requirements for cabinets of complete switchgears for voltages above 1000 V) and GOST 12.2.007.4-96, as well as design documentation.
Due to constant work to improve the product, increasing its reliability and improving operation, changes may be made to the design that are not reflected in this publication.
Main settings | |
Name of parameters |
Values |
Rated voltage, kV |
6 |
Highest operating voltage, kV |
7,2 |
Rated current of the main circuits, A: a) incoming and sectional cabinets |
315, 400, 630 |
Rated shutdown current, kA, no more:
|
10 |
Normalized parameters of the switching current, kA: largest peak |
25 |
Electrodynamic resistance current, kA, not less |
25 |
Thermal resistance current, kA |
10 |
Thermal current flow time, s |
1 |
Mining marking according to GOST 24754-81 |
RN1 |
Shell protection degree according to GOST 14254-96, not less |
IP54 |
Execution of outgoing lines (cable, overhead, busbar) |
cable |
The maximum permissible number of switching operations without inspection of the rated current of the cabinet |
30000 |
Rated voltage of auxiliary circuits, V |
110 |
No-load value switched off by disconnecting |
0,6 |
Insulation level according to GOST 1516.1-76 |
normal |
Type of insulation |
combined |
Availability of pull-out elements in cabinets |
with retractable elements |
Type of linear high-voltage connections |
cable |
Cabinet service conditions |
two-way |
Maximum number of high-voltage cables in cabinets with |
4 |
Largest cross-section of high voltage cables, sq. mm. |
3×240 |
Switch type |
vacuum |
Disconnector type |
plug power |
The overall dimensions of the cabinets are the same for all versions:
|
1700mm; |
Climatic modification and placement category according to GOST |
UHL5 |
Note: *The highest operating voltage of 7.2 kV refers to the switching capacity and insulation of the breaker and cabinet.
*Electrodynamic and thermal resistance is determined by the technical parameters of current transformers.
Distribution devices of the CS-MN series are designed for the distribution of electrical energy in networks with a voltage of 6 kV with an isolated neutral with a frequency of 50 Hz, protection of electrical installations and control of underground electrical receivers in iron ore and coal mines. CS-MN multi-cabinet, indoor installation, stationary, double-sided service, with withdrawable elements, with local and remote control. CS-MN cabinets are used to complete distribution points and can be connected into separate sections. The sections are connected to each other by a sectional cabinet. The distribution point may consist of one, two or three sections. CDD-MN cabinets and the products attached to them are of normal mine design.
Cabinets of the CS-MN series comply with the requirements of GOST 24754-2013 (regarding the requirements for cabinets of complete switchgears for voltages above 1000 V) and GOST 12.2.007.4-96, as well as design documentation.
The main advantages of cabinets of the CS-MN series:
Terms of Use:
-nominal values of climatic factors according to GOST 15150-69 and GOST 15543.1-89