Complete switchgear (CS) for mining in the normal version MN of the CDD-MN series

Distribution devices of the CS-MN series are designed for the distribution of electrical energy in networks with a voltage of 6 kV with an isolated neutral with a frequency of 50 Hz, protection of electrical installations and control of underground electrical receivers in iron ore and coal mines. CS-MN multi-cabinet, indoor installation, stationary, double-sided service, with withdrawable elements, with local and remote control. CS-MN cabinets are used to complete distribution points and can be connected into separate sections. The sections are connected to each other by a sectional cabinet. The distribution point may consist of one, two or three sections. CS-MN cabinets and the products attached to them are of normal mine design.

Cabinets of the CS-MN series comply with the requirements of GOST 24754-2013 (regarding the requirements for cabinets of complete switchgears for voltages above 1000 V) and GOST 12.2.007.4-96, as well as design documentation.

Due to constant work to improve the product, increasing its reliability and improving operation, changes may be made to the design that are not reflected in this publication.

Main settings

Name of parameters

Values

Rated voltage, kV

6

Highest operating voltage, kV

7,2

Rated current of the main circuits, A: a) incoming and sectional cabinets
b) outgoing connection cabinets

315, 400, 630
100, 160, 200, 315, 400

Rated shutdown current, kA, no more:

  1. cabinet
  2. switch

10
20

Normalized parameters of the switching current, kA: largest peak
initial effective value of the periodic component

25
10

Electrodynamic resistance current, kA, not less

25

Thermal resistance current, kA

10

Thermal current flow time, s

1

Mining marking according to GOST 24754-81

RN1

Shell protection degree according to GOST 14254-96, not less

IP54

Execution of outgoing lines (cable, overhead, busbar)

cable

The maximum permissible number of switching operations without inspection of the rated current of the cabinet

30000

Rated voltage of auxiliary circuits, V

110
220

No-load value switched off by disconnecting
contacts of withdrawable elements for 6 kV, A

0,6

Insulation level according to GOST 1516.1-76

normal

Type of insulation

combined

Availability of pull-out elements in cabinets

with retractable elements

Type of linear high-voltage connections

cable

Cabinet service conditions

two-way

Maximum number of high-voltage cables in cabinets with
a circuit breaker

4

Largest cross-section of high voltage cables, sq. mm.

3×240

Switch type

vacuum

Disconnector type

plug power

The overall dimensions of the cabinets are the same for all versions:

  1. height
  2. depth
  3. width

1700mm;
1400mm;
800mm

Climatic modification and placement category according to GOST
15150-69.

UHL5

Note: *The highest operating voltage of 7.2 kV refers to the switching capacity and insulation of the breaker and cabinet.
*Electrodynamic and thermal resistance is determined by the technical parameters of current transformers.

Distribution devices of the CS-MN series are designed for the distribution of electrical energy in networks with a voltage of 6 kV with an isolated neutral with a frequency of 50 Hz, protection of electrical installations and control of underground electrical receivers in iron ore and coal mines. CS-MN multi-cabinet, indoor installation, stationary, double-sided service, with withdrawable elements, with local and remote control. CS-MN cabinets are used to complete distribution points and can be connected into separate sections. The sections are connected to each other by a sectional cabinet. The distribution point may consist of one, two or three sections. CDD-MN cabinets and the products attached to them are of normal mine design.
Cabinets of the CS-MN series comply with the requirements of GOST 24754-2013 (regarding the requirements for cabinets of complete switchgears for voltages above 1000 V) and GOST 12.2.007.4-96, as well as design documentation.
The main advantages of cabinets of the CS-MN series:

  1. increased reliability in operation due to the use of modern high-voltage switching devices with a high mechanical and switching life;
  2. use only copper busbars;
  3. relay protection is provided through the use of modern microprocessor units;
  4. placement of auxiliary circuit equipment in a separate removable relay cabinet, which is completely isolated from power current-carrying circuits;

Terms of Use:

  1. ambient temperature from -10˚С to +45˚С;
  2. relative humidity up to 100% at a temperature of 35˚C;
  3. altitude above sea level – no more than 1000 m;
  4. working position in space – vertical (permissible deviation of 0.17 rad in any direction);
  5. dust content in the ambient air up to 8 mg/m3, dust is non-flammable, non-explosive, conductive;
  6. the environment should not contain caustic vapors and gases in concentrations that destroy metal and insulation;
  7. the device must be protected from direct contact with water;

-nominal values ​​of climatic factors according to GOST 15150-69 and GOST 15543.1-89

    Ask a question

    Your name

    • E-mail

    • Phone number

    Your question

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service.

    Submit

      Request a call

      Your name

      Your phone number

      This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service.

      Submit

        Заказать продукт

        Ваше имя

        • E-mail

        • Телефон

        Сообщение

        Этот сайт защищен reCAPTCHA, а также Политикой конфиденциальности и Условиями обслуживания Google.

        Отправить